Nominal Operating
Capacity |
Grease Volume
|
Nominal Inside Dimensions |
Inlet / Outlet** |
| (gal) |
(gal / lbs) |
Diameter |
Length |
Diameter |
* 240 |
63.4 / 483 |
3’ 2” |
4’ 0” |
4” |
* 300 |
76.4 / 581 |
3’ 2” |
5’ 0” |
4” |
550 |
137 / 1,041 |
3’ 6” |
7’ 9” |
4” |
750 |
190 / 1,444 |
3’ 6”
|
10’ 9” |
4” |
1,000 |
246 / 1,875 |
4’ 0”
|
10’ 9” |
6” |
1,500 |
403 / 3,065 |
5’ 4” |
9’ 0” |
6” |
2,000 |
514 / 3,906 |
5’ 4” |
12’ 0” |
8” |
2,500 |
643 / 4,886 |
5’ 4”
|
15’ 0” |
8” |
3,000 |
771 / 5,861 |
5’ 4” |
18’-0” |
8” |
4,000 |
1,028 / 7,817 |
5’ 4” |
24’ 0” |
8” |
5,000 |
1,245 / 9,464 |
6’ 0” |
23’ 10” |
10” |
6,000 |
1,497 / 11,383 |
6’ 0” |
28’ 8” |
10” |
7,000 |
1.847 / 14,040 |
7’ 0” |
24’ 4” |
10” |
8,000 |
2.666 / 20,264 |
7’ 0” |
28’ 0” |
10” |
9,000 |
2,349 / 17,858 |
8’ 0” |
24’ 0” |
12” |
10,000 |
2,611 / 19,842 |
8’ 0” |
26’ 8” |
12” |
12,000 |
3,133 / 23,811 |
8’ 0” |
32’ 0” |
12” |
15,000 |
5,000 / 37,996 |
10’ 0”
|
25’ 6” |
14” |
20,000 |
5,413 / 41,140 |
10’ 6” |
31’ 0” |
16” |
25,000 |
6,544 / 49,738 |
10’ 6” |
38’ 9” |
18” |
30,000 |
7,580 / 57,606 |
10’ 6”
|
46’ 6” |
20” |
40,000 |
10,035 / 76,369 |
12’ 0” |
47’ 6” |
24” |
50,000 |
12,570 / 95,538 |
12’ 0” |
59’ 6" |
24” |
* - One Manway, Single-Basin & Double-Basin ONLY. ** NPT for 4-6" Inlet and Outlet, 8" and larger will be Flanged Connections. Gravity Grease Interceptor (GGI) sizing and construction is consistent with industry protocol for complying with the sewer pre-treatment regulations. GGI sizing is based on 30-minute retention time. Drain-Net for alternate sizing methods. |